The short-circuit test results of 6.9 kV/2.3 kV 400 kVA-class YBCO model transformer
We are developing an elemental technology for 66 kV/6.9 kV 20 MVA-class power transformer with YBCO conductors. The protection of short-circuit technology is one of the elemental technologies for HTS transformer. Since short-circuit current is much higher than critical current of YBCO tape, there is...
Gespeichert in:
Veröffentlicht in: | Physica. C, Superconductivity Superconductivity, 2011-11, Vol.471 (21-22), p.1374-1378 |
---|---|
Hauptverfasser: | , , , , , , , , , , , |
Format: | Artikel |
Sprache: | eng |
Schlagworte: | |
Online-Zugang: | Volltext |
Tags: |
Tag hinzufügen
Keine Tags, Fügen Sie den ersten Tag hinzu!
|
Zusammenfassung: | We are developing an elemental technology for 66 kV/6.9 kV 20 MVA-class power transformer with YBCO conductors. The protection of short-circuit technology is one of the elemental technologies for HTS transformer. Since short-circuit current is much higher than critical current of YBCO tape, there is a possibility that superconducting characteristics may be damaged during short-circuit period. We made a conductor to compose the YBCO tape with copper tape. We manufactured 6.9 kV/2.3 kV 400 kVA-class YBCO model transformer using this conductor and performed short-circuit current test. The short-circuit current of primary winding was 346 A which was about six times larger than the rated current. The I-V characteristics of the winding did not change before and after the test. We may consider this conductor withstands short-circuit current. |
---|---|
ISSN: | 0921-4534 |
DOI: | 10.1016/j.physc.2011.05.197 |