A New Method to Evaluate the Short-Time Withstand Current for Air Circuit Breaker
Short-time withstand current is one of the crucial nominal parameters in air circuit breaker. A numerical method to evaluate the short-time withstand current is proposed. Cylindrical current carrying bridge is introduced to describe the contact spot between movable and fixed contacts. Taking into ac...
Gespeichert in:
Veröffentlicht in: | IEICE Transactions on Electronics 2008/08/01, Vol.E91.C(8), pp.1292-1298 |
---|---|
Hauptverfasser: | , , , |
Format: | Artikel |
Sprache: | eng |
Schlagworte: | |
Online-Zugang: | Volltext |
Tags: |
Tag hinzufügen
Keine Tags, Fügen Sie den ersten Tag hinzu!
|
Zusammenfassung: | Short-time withstand current is one of the crucial nominal parameters in air circuit breaker. A numerical method to evaluate the short-time withstand current is proposed. Cylindrical current carrying bridge is introduced to describe the contact spot between movable and fixed contacts. Taking into account the action of ferromagnetic splitter plates, the variation of the conductor properties with temperature and the variation of contact spot radius with the electro-dynamic repulsion force, a transient finite element calculation model is developed by coupling the electromagnetic field and thermal field. The loaded short circuit current is considered as the short-time withstand current once the highest temperature is near to the melting point of the contact material. It demonstrates that the method is useful to evaluate the performance of the air circuit breaker. |
---|---|
ISSN: | 0916-8524 1745-1353 1745-1353 |
DOI: | 10.1093/ietele/e91-c.8.1292 |