Parameter identification of interconnected power system frequency after trip-out of high voltage transmission line

Accurate modeling and parameters of high voltage (HV) grid are critical for stability research of system frequency. In this paper, simulation modeling of the system frequency was conducted of an interconnected power system with HV transmission lines in China. Based on recorded tripping data of the H...

Ausführliche Beschreibung

Gespeichert in:
Bibliographische Detailangaben
Veröffentlicht in:Frontiers in Energy 2014-09, Vol.8 (3), p.386-393
Hauptverfasser: ZHOU, Xuzhan, LIU, Shanshan, WANG, Mingkun, DAI, Yiping, TANG, Yaohua
Format: Artikel
Sprache:eng
Schlagworte:
Online-Zugang:Volltext
Tags: Tag hinzufügen
Keine Tags, Fügen Sie den ersten Tag hinzu!
Beschreibung
Zusammenfassung:Accurate modeling and parameters of high voltage (HV) grid are critical for stability research of system frequency. In this paper, simulation modeling of the system frequency was conducted of an interconnected power system with HV transmission lines in China. Based on recorded tripping data of the HV transmission lines, system parameters were identified by using genetic algorithm (GA). The favorable agreement between simulation results and recorded data verifies the validity of gird models and the accuracy of system parameters. The results of this paper can provide reference for the stability research of HV power grid.
ISSN:2095-1701
2095-1698
DOI:10.1007/s11708-014-0323-9