The performance of novel compact heat exchangers with highly extended surfaces

The performance of highly extended surface heat exchangers has been evaluated in two heat pump applications: as the evaporator in a compression heat pump and as the absorber in an absorption heat transformer. Film heat transfer coefficients based on the equivalent plain tube area (p.t.a.), ranged fr...

Ausführliche Beschreibung

Gespeichert in:
Bibliographische Detailangaben
Veröffentlicht in:Applied thermal engineering 1996, Vol.16 (3), p.245-254
Hauptverfasser: Currie, J.S., Low, R.E., Pritchard, C.L.
Format: Artikel
Sprache:eng
Schlagworte:
Online-Zugang:Volltext
Tags: Tag hinzufügen
Keine Tags, Fügen Sie den ersten Tag hinzu!
Beschreibung
Zusammenfassung:The performance of highly extended surface heat exchangers has been evaluated in two heat pump applications: as the evaporator in a compression heat pump and as the absorber in an absorption heat transformer. Film heat transfer coefficients based on the equivalent plain tube area (p.t.a.), ranged from 200 W m −2 K −1, for gas-liquid contact, to 3800 Wm −2 K −1, in the evaporation of a liquid stream. Another measure of the heat transfer characteristics of the exchangers were the ‘ UA o’ values, which were significantly better than the theoretical values calculated for each operation. The experimental results ranged from 12 W K −1 (gas) to 214 W K −1 (evaporation), while the theoretical values were 1 W K −1 (gas) and 43 K −1 (evaporation).
ISSN:1359-4311
DOI:10.1016/1359-4311(95)00072-0