Thermal Assessment of an Air-Filled Surface Trough for 400 kV Cables

Using a full-scale trough, temperature measurements around the cables and inside the trough yield an empirical formula for heat transfer from the central cable. This, together with assumed solar and wind quantities at the ground surface and the effective thermal resistance of the trough via the soil...

Ausführliche Beschreibung

Gespeichert in:
Bibliographische Detailangaben
Veröffentlicht in:Electric power systems research 1988-08, Vol.15 (1), p.1-5
1. Verfasser: Weedy, B.M.
Format: Artikel
Sprache:eng
Schlagworte:
Online-Zugang:Volltext
Tags: Tag hinzufügen
Keine Tags, Fügen Sie den ersten Tag hinzu!
Beschreibung
Zusammenfassung:Using a full-scale trough, temperature measurements around the cables and inside the trough yield an empirical formula for heat transfer from the central cable. This, together with assumed solar and wind quantities at the ground surface and the effective thermal resistance of the trough via the soil to ambient, yields the thermal resistance of the cable surface to ambient. Calculation of the current rating of the cables yields a value below the normal buried rating. It is concluded that the air-filled trough has no advantage over the sand-filled variety.
ISSN:0378-7796
1873-2046
DOI:10.1016/0378-7796(88)90033-8