A contribution to the compensation of extra high voltage transmission lines

An improved method to design suitable compensating schemes for extra high voltage transmission lines is presented. The technique is general and effective and will greatly facilitate the design of the optimal compensation scheme for extra high voltage transmission lines. The technique is illustrated...

Ausführliche Beschreibung

Gespeichert in:
Bibliographische Detailangaben
Veröffentlicht in:Electric power systems research 1987-04, Vol.12 (2), p.113-123
Hauptverfasser: Prusty, S., Sanyal, S.K., Satapathy, J.K.
Format: Artikel
Sprache:eng
Schlagworte:
Online-Zugang:Volltext
Tags: Tag hinzufügen
Keine Tags, Fügen Sie den ersten Tag hinzu!
Beschreibung
Zusammenfassung:An improved method to design suitable compensating schemes for extra high voltage transmission lines is presented. The technique is general and effective and will greatly facilitate the design of the optimal compensation scheme for extra high voltage transmission lines. The technique is illustrated for a typical 500 kV system. The equations developed here for voltage maxima and minima along the transmission line eliminate the need for point-to-point computation of the voltage profile. The controversy existing in the literature over the problem of making a choice between pi and tee configurations has been removed and it is established with a mathematical proof that the tee configuration requires compensating elements of lower ratings.
ISSN:0378-7796
1873-2046
DOI:10.1016/0378-7796(87)90029-0