Effect of connection type on galvanic corrosion between lead and copper pipes

Pipe connectors can significantly influence galvanic corrosion between lead and copper pipes by distancing the lead from copper pipe, introducing a third metal, and forming crevices. In this study, the effects of distance, connector material, and crevices on galvanic corrosion were examined, and ben...

Ausführliche Beschreibung

Gespeichert in:
Bibliographische Detailangaben
Veröffentlicht in:Journal - American Water Works Association 2013-10, Vol.105 (10), p.E576-E586
Hauptverfasser: Clark, Brandi, Cartier, Clément, Clair, Justin St, Triantafyllidou, Simoni, Prévost, Michèle, Edwards, Marc
Format: Artikel
Sprache:eng
Schlagworte:
Online-Zugang:Volltext
Tags: Tag hinzufügen
Keine Tags, Fügen Sie den ersten Tag hinzu!
Beschreibung
Zusammenfassung:Pipe connectors can significantly influence galvanic corrosion between lead and copper pipes by distancing the lead from copper pipe, introducing a third metal, and forming crevices. In this study, the effects of distance, connector material, and crevices on galvanic corrosion were examined, and bench-scale comparison testing of commercial connectors was conducted using real tap waters. Brass connectors were found to only slightly decrease (25%) the galvanic current that sacrifices, or corrodes, lead pipe, with higher reductions for brasses with higher zinc content. Crevices in brass connectors contained water with extremely high levels of lead (up to 9.4 × 106µg/L); in bench-scale tests, crevices produced approximately four times more lead release to the water than did direct connections.
ISSN:0003-150X
1551-8833
DOI:10.5942/jawwa.2013.105.0113