Failure Mechanisms of Shielded Power Cable Related to High Ground Shield Resistance and/or Insulation of Neutral Wires from the Ground Shield

A number of conditions can cause separation of the neutral wires from the semiconducting ground shield or cause a large increase in the resistivity of the wound shield. Such conditions can lead to (i) the ground shield becoming effectively floating or (ii) the ground shield acting as a dielectric ra...

Ausführliche Beschreibung

Gespeichert in:
Bibliographische Detailangaben
Veröffentlicht in:IEEE power engineering review 2001-12, Vol.21 (12), p.68-68
1. Verfasser: Boggs, S. A.
Format: Artikel
Sprache:eng
Schlagworte:
Online-Zugang:Volltext bestellen
Tags: Tag hinzufügen
Keine Tags, Fügen Sie den ersten Tag hinzu!
Beschreibung
Zusammenfassung:A number of conditions can cause separation of the neutral wires from the semiconducting ground shield or cause a large increase in the resistivity of the wound shield. Such conditions can lead to (i) the ground shield becoming effectively floating or (ii) the ground shield acting as a dielectric rather than a conductor. In either case, this can lead to partial discharge under normal operating voltage and/or lightning surge-induced flashover between the neutral wires and ground shield, conditions that can cause cable failure. The theoretical context of these conditions is examined, after which a concrete example, which has resulted in field failures, is provided.