Power transformer temperature evaluation for overloading conditions

The calculation methodologies of transformers' hottest spot and top oil temperatures are evaluated in this paper. Thereafter, a comparison between the calculated and the values obtained during the assessment of a transformer factory test was realized. The referred tests were conducted using an...

Ausführliche Beschreibung

Gespeichert in:
Bibliographische Detailangaben
Veröffentlicht in:IEEE transactions on power delivery 2005-01, Vol.20 (1), p.179-184
Hauptverfasser: Jardini, J.A., Brittes, J.L.P., Magrini, L.C., Bini, M.A., Yasuoka, J.
Format: Artikel
Sprache:eng
Schlagworte:
Online-Zugang:Volltext bestellen
Tags: Tag hinzufügen
Keine Tags, Fügen Sie den ersten Tag hinzu!
Beschreibung
Zusammenfassung:The calculation methodologies of transformers' hottest spot and top oil temperatures are evaluated in this paper. Thereafter, a comparison between the calculated and the values obtained during the assessment of a transformer factory test was realized. The referred tests were conducted using an ONAF type, 30/40 MVA, 138/13.8 kV transformer, in which sensors with fiber-optic cables, to record directly the internal parameters, were installed. In a first series of tests, transformer loadings corresponding to 100%, 70% and 116.5% of rated power, were used. The tests were completed by applying values of a daily load profile with several hourly power levels. Additionally, in two of the hourly periods, high temporary loadings one of 160% during 30 minutes, and another of 170% during 15 minutes, were applied.