Power transformer temperature evaluation for overloading conditions
The calculation methodologies of transformers' hottest spot and top oil temperatures are evaluated in this paper. Thereafter, a comparison between the calculated and the values obtained during the assessment of a transformer factory test was realized. The referred tests were conducted using an...
Gespeichert in:
Veröffentlicht in: | IEEE transactions on power delivery 2005-01, Vol.20 (1), p.179-184 |
---|---|
Hauptverfasser: | , , , , |
Format: | Artikel |
Sprache: | eng |
Schlagworte: | |
Online-Zugang: | Volltext bestellen |
Tags: |
Tag hinzufügen
Keine Tags, Fügen Sie den ersten Tag hinzu!
|
Zusammenfassung: | The calculation methodologies of transformers' hottest spot and top oil temperatures are evaluated in this paper. Thereafter, a comparison between the calculated and the values obtained during the assessment of a transformer factory test was realized. The referred tests were conducted using an ONAF type, 30/40 MVA, 138/13.8 kV transformer, in which sensors with fiber-optic cables, to record directly the internal parameters, were installed. In a first series of tests, transformer loadings corresponding to 100%, 70% and 116.5% of rated power, were used. The tests were completed by applying values of a daily load profile with several hourly power levels. Additionally, in two of the hourly periods, high temporary loadings one of 160% during 30 minutes, and another of 170% during 15 minutes, were applied. |
---|---|