Nine-phase armature windings design, test, and harmonic analysis
A nine-phase armature winding was developed for a large generator. Alternative methods for interconnecting the pole-phase groups were examined. An alternate-pole connection scheme was adopted and a prototype induction motor was constructed to confirm the winding scheme. Since only a three-phase powe...
Gespeichert in:
Veröffentlicht in: | IEEE transactions on magnetics 2005-01, Vol.41 (1), p.299-302 |
---|---|
Hauptverfasser: | , , |
Format: | Artikel |
Sprache: | eng |
Schlagworte: | |
Online-Zugang: | Volltext bestellen |
Tags: |
Tag hinzufügen
Keine Tags, Fügen Sie den ersten Tag hinzu!
|
Zusammenfassung: | A nine-phase armature winding was developed for a large generator. Alternative methods for interconnecting the pole-phase groups were examined. An alternate-pole connection scheme was adopted and a prototype induction motor was constructed to confirm the winding scheme. Since only a three-phase power source was available for testing, the induction motor was tested by using three, three-phase winding sections, one at a time. Air-gap harmonic fields produced some unusual results. These test results and harmonic analyses to explain them are presented herein. The tests confirmed the nine-phase winding scheme that was adopted. The harmonic analyses revealed that the complete nine-phase winding exhibited a very low harmonic content, a distinct advantage of a nine-phase winding for future applications. |
---|---|
ISSN: | 0018-9464 1941-0069 |
DOI: | 10.1109/TMAG.2004.839288 |