Effect of Transfer Coefficients on MV and LV Flicker Levels

It has been suggested that the recommended flicker planning levels provided in IEC 61000 3-7 and IEEE 1453 are too restrictive for high-voltage and extra-high-voltage networks. The premise of this argument is based on a perceived increase in low-voltage (LV) flicker compatibility level. Some believe...

Ausführliche Beschreibung

Gespeichert in:
Bibliographische Detailangaben
Veröffentlicht in:IEEE transactions on power delivery 2011-04, Vol.26 (2), p.632-639
Hauptverfasser: Horton, R, Haskew, T A
Format: Artikel
Sprache:eng
Schlagworte:
Online-Zugang:Volltext bestellen
Tags: Tag hinzufügen
Keine Tags, Fügen Sie den ersten Tag hinzu!
Beschreibung
Zusammenfassung:It has been suggested that the recommended flicker planning levels provided in IEC 61000 3-7 and IEEE 1453 are too restrictive for high-voltage and extra-high-voltage networks. The premise of this argument is based on a perceived increase in low-voltage (LV) flicker compatibility level. Some believe that flicker measurements made in Europe over a period of several years support the notion of an increased LV compatibility level; however, measurements performed by the authors in North America indicate otherwise. Analysis of authors' measurements suggests that the lack of customer complaints is due primarily to the effect of flicker transfer coefficients, rather than a presumed increase in LV compatibility level, and supports the continued use of P st95% =1.0 as the LV flicker compatibility level.
ISSN:0885-8977
1937-4208
DOI:10.1109/TPWRD.2009.2036015