STUDIES ON COOLING OPERATION OF TABS COMBINED WITH FLOOR SUPPLY DISPLACEMENT AIR CONDITIONING SYSTEM
The cooling operational performance of TABS combined with floor supply displacement air conditioning system adopted in the Tohoku Branch of S company was investigated. The purpose of this research was to evaluate four control methods and clarify their energy consumption efficiency and load leveling...
Gespeichert in:
Veröffentlicht in: | AIJ Journal of Technology and Design 2024/06/20, Vol.30(75), pp.832-837 |
---|---|
Hauptverfasser: | , , , , |
Format: | Artikel |
Sprache: | jpn |
Schlagworte: | |
Online-Zugang: | Volltext |
Tags: |
Tag hinzufügen
Keine Tags, Fügen Sie den ersten Tag hinzu!
|
Zusammenfassung: | The cooling operational performance of TABS combined with floor supply displacement air conditioning system adopted in the Tohoku Branch of S company was investigated. The purpose of this research was to evaluate four control methods and clarify their energy consumption efficiency and load leveling effects. By operating with the proposed control method, the peak amount of received power was reduced by approximately 10%, confirming high energy consumption efficiency. Additionally, a thermal environment was created in the office as planned, with small temperature differences. |
---|---|