EFFECTS OF LOCAL NON-ISOTHERMAL AIRFLOW DURING NATURAL VENTILATION ON INDOOR COMFORTABLE TEMPERATURE: Subject experiment at room temperature 22℃ and 29

In this study, we aimed to clarify the effect on comfortable room temperature when various local low-temperature airflows occur during natural ventilation, and calculated PMV-teq from the body equivalent temperature of the thermal manikin experiment. Comparisons were made with the thermal sensation...

Ausführliche Beschreibung

Gespeichert in:
Bibliographische Detailangaben
Veröffentlicht in:AIJ Journal of Technology and Design 2024/06/20, Vol.30(75), pp.820-825
Hauptverfasser: YAMAMOTO, Yoshihide, ITO, Shiho
Format: Artikel
Sprache:jpn
Schlagworte:
Online-Zugang:Volltext
Tags: Tag hinzufügen
Keine Tags, Fügen Sie den ersten Tag hinzu!
Beschreibung
Zusammenfassung:In this study, we aimed to clarify the effect on comfortable room temperature when various local low-temperature airflows occur during natural ventilation, and calculated PMV-teq from the body equivalent temperature of the thermal manikin experiment. Comparisons were made with the thermal sensation results of subject experiments under these conditions. As a result of the subject experiment, under the 29℃ condition, the PMV-teq and the average thermal sensation value were close to each other. However, under conditions of 22℃, the subjects felt colder than expected based on PMV-teq, and it seemed necessary to consider local discomfort as well.
ISSN:1341-9463
1881-8188
DOI:10.3130/aijt.30.820