A Novel Series 24-Pulse Rectifier Operating in Low Harmonic State Based on Auxiliary Passive Injection at DC Side

To reduce the current harmonics on the input side of a multi-pulse rectifier, this paper proposes a low harmonic current source series multi-pulse rectifier based on an auxiliary passive injection circuit at the DC side. The rectifier only needs to add an auxiliary passive injection circuit on the D...

Ausführliche Beschreibung

Gespeichert in:
Bibliographische Detailangaben
Veröffentlicht in:Electronics (Basel) 2024-03, Vol.13 (6), p.1160
Hauptverfasser: Chen, Xiaoqiang, Bai, Tun, Wang, Ying, Gong, Jiangyun, Mu, Xiuqing, Chang, Zhanning
Format: Artikel
Sprache:eng
Schlagworte:
Online-Zugang:Volltext
Tags: Tag hinzufügen
Keine Tags, Fügen Sie den ersten Tag hinzu!
Beschreibung
Zusammenfassung:To reduce the current harmonics on the input side of a multi-pulse rectifier, this paper proposes a low harmonic current source series multi-pulse rectifier based on an auxiliary passive injection circuit at the DC side. The rectifier only needs to add an auxiliary passive injection circuit on the DC side of the series 12-pulse rectifier, which can change its AC input voltage from 12-step waves to 24-step waves. We analyzed the working mode of the rectifier, optimized the optimal turn ratio of the injection transformer from the perspective of minimizing the total harmonic distortion (THD) value of the input voltage on the AC side, and analyzed the diode open circuit fault in the auxiliary passive injection circuit. Test verification shows that, after using the passive harmonic injection circuit, the THD value of the input voltage of the AC side of the rectifier is reduced from 14.03% to 4.86%. The THD value of the input current is reduced from 5.30% to 2.16%. The input power factor has been increased from 98.86% to 99.83%, and the power quality has been improved.
ISSN:2079-9292
2079-9292
DOI:10.3390/electronics13061160