Operation of the DC Link in the Conditions of Poor Quality of Grid Power

The HVDC link at the Trans-Baikal Converter Complex at the 220 kV Mogocha Substation operates under conditions of poor quality of power in the grid. Distortions in a grid are characterized by values of the negative-sequence voltage unbalance factor and voltage THD that are many times higher than the...

Ausführliche Beschreibung

Gespeichert in:
Bibliographische Detailangaben
Veröffentlicht in:Power technology and engineering 2022-07, Vol.56 (2), p.280-289
Hauptverfasser: Kiselev, A. N., Peshkov, M. V., Plotnikova, T. V., Sokur, P. V., Shamonov, R. G.
Format: Artikel
Sprache:eng
Schlagworte:
Online-Zugang:Volltext
Tags: Tag hinzufügen
Keine Tags, Fügen Sie den ersten Tag hinzu!
Beschreibung
Zusammenfassung:The HVDC link at the Trans-Baikal Converter Complex at the 220 kV Mogocha Substation operates under conditions of poor quality of power in the grid. Distortions in a grid are characterized by values of the negative-sequence voltage unbalance factor and voltage THD that are many times higher than the rated values. The operation of STATCOMs, which are part of the HVDC link, has a beneficial effect on the quality of power across the 220 kV buses of the Mogocha Substation. However, a STATCOM is additionally loaded by negative-sequence currents and higher-harmonic currents. A mathematical model was developed and calculations were carried out for various modes of operation to estimate the available power output of the HVDC link in conditions of poor quality of grid power.
ISSN:1570-145X
1570-1468
DOI:10.1007/s10749-023-01507-x