Experimental Registration and Numerical Simulation of the Transient Overvoltages Caused by Single Phase Intermittent Arc Earth Fault in 35 kV Network With Isolated Neutral
The paper presents the results of experimental registrations and numerical simulations of the transient overvoltages caused by single phase intermittent arc earth fault in 35 kV network with isolated neutral. Experimental laboratory investigation is performed in order to implement appropriate arc fa...
Gespeichert in:
Veröffentlicht in: | IEEE transactions on power delivery 2022-06, Vol.37 (3), p.1795-1802 |
---|---|
Hauptverfasser: | , |
Format: | Artikel |
Sprache: | eng |
Schlagworte: | |
Online-Zugang: | Volltext bestellen |
Tags: |
Tag hinzufügen
Keine Tags, Fügen Sie den ersten Tag hinzu!
|
Zusammenfassung: | The paper presents the results of experimental registrations and numerical simulations of the transient overvoltages caused by single phase intermittent arc earth fault in 35 kV network with isolated neutral. Experimental laboratory investigation is performed in order to implement appropriate arc fault model for arcs with low and discontinuous current. Single phase to earth arc fault is created in field in 35 kV network. Numerical model of the system is created in EMTP-ATP software. Overvoltage waveshapes and overvoltage factors are calculated and compared to measured values. Good agreement between the measured and calculated results is achieved. |
---|---|
ISSN: | 0885-8977 1937-4208 |
DOI: | 10.1109/TPWRD.2021.3098829 |