Experimental Investigation of Near- and Supercritical Heat Transfer to R125 Flowing in a Horizontal Tube

•Supercritical heat transfer to R125 in horizontal tube with inner diameter 24.77 mm.•Pressure influence on heat transfer insignificant under each operating condition.•Detrimental effect of increasing heat flux more pronounced at higher mass fluxes.•In general amelioration in heat transfer coefficie...

Ausführliche Beschreibung

Gespeichert in:
Bibliographische Detailangaben
Veröffentlicht in:International journal of heat and mass transfer 2022-02, Vol.183, p.122179, Article 122179
Hauptverfasser: Van Nieuwenhuyse, J., De Meulemeester, A., Lecompte, S., De Paepe, M.
Format: Artikel
Sprache:eng
Schlagworte:
Online-Zugang:Volltext
Tags: Tag hinzufügen
Keine Tags, Fügen Sie den ersten Tag hinzu!
Beschreibung
Zusammenfassung:•Supercritical heat transfer to R125 in horizontal tube with inner diameter 24.77 mm.•Pressure influence on heat transfer insignificant under each operating condition.•Detrimental effect of increasing heat flux more pronounced at higher mass fluxes.•In general amelioration in heat transfer coefficient for increase in mass flux.•Majority of evaluated correlations underestimate actual heat transfer. Knowledge about supercritical heat transfer to refrigerants with horizontal flow is scarce and experimental data is mostly lacking. This makes an accurate sizing of heat exchangers impossible. In addition, the majority of the tested geometries in literature are limited to an inner diameter of only 16 mm. In order to close the gap and increase the knowledge about supercritical heat transfer, a novel experimental setup was used to investigate supercritical heat transfer phenomena on larger tube diameters. The test section consists of a horizontal counter current tube-in-tube heat exchanger. R125 flows in the inner tube having an inner diameter of 24.77 mm. The influence of mass flux (226 - 585 kg/m2s), heat flux (7.7 - 21.9 kW/m2) and supercritical pressure (3.7 - 4.1 MPa, corresponding to 1.03 - 1.12 times the critical pressure) on local forced convective heat transfer was investigated. No visible influence of pressure on the convective heat transfer coefficient is noticed, indicating that buoyancy is present and influential in the performed measurements. The applied heat flux does have an effect, with a decrease in the heat transfer coefficient for an increase in heat flux. This effect is more pronounced at higher mass fluxes. At high mass flux, increasing the heat flux with 42% results in a drop in heat transfer coefficient of 46%, while this is only 40% and 26% at medium and low mass flux, respectively. However, there appears to be a limit to this detrimental effect at higher mass fluxes. Finally, heat transfer increases for an increase in mass flux. Increasing the mass flux with 76% results on average in a rise in heat transfer coefficient of 88%, for measurements at medium heat flux. At high heat fluxes, an increase of 71% is observed for a rise in mass flux of 59%. Nine heat transfer correlations are evaluated. The majority underestimates the heat transfer significantly, however, two correlations operate adequately and are proposed as a basis for future correlation development. The unique dataset and insights presented in this work enable a better understand
ISSN:0017-9310
1879-2189
DOI:10.1016/j.ijheatmasstransfer.2021.122179