An Adaptive Protection Scheme for Power Systems Considering the Effects of HVDC Interfaced Distributed Generations

Distributed Generations are usually connected to the ac grid through HVDC transmission systems. However, due to the current injected by the grid-side voltage source converter (GVSC), the voltage drop after a short-circuit fault will be partly compensated. For this reason, the viewed impedance of dis...

Ausführliche Beschreibung

Gespeichert in:
Bibliographische Detailangaben
Veröffentlicht in:IEEE access 2022-01, Vol.10, p.1-1
Hauptverfasser: Jipu, Gao, Xiaobo, Li, Mingyong, Xin, Yang, Yu, Changbao, Xu
Format: Artikel
Sprache:eng
Schlagworte:
Online-Zugang:Volltext
Tags: Tag hinzufügen
Keine Tags, Fügen Sie den ersten Tag hinzu!
Beschreibung
Zusammenfassung:Distributed Generations are usually connected to the ac grid through HVDC transmission systems. However, due to the current injected by the grid-side voltage source converter (GVSC), the voltage drop after a short-circuit fault will be partly compensated. For this reason, the viewed impedance of distance relays will be affected, which is a challenge for the distance protection scheme. For this issue, this paper proposed an adaptive distance protection scheme for the system containing distributed generations. Firstly, the proposed scheme controls the current of the GSVC to be proportional to the current of the AC transmission line. Secondly, an adaptive distance protection criterion is proposed, which can obtain the impedance from the relay to the fault-point accurately. The effectiveness of the proposed approach was validated through simulation using MATLAB/Simulink.