Performance Evaluation of a Maisotsenko Cycle Cooling Tower with Uneven Length of Dry and Wet Channels in Hot and Humid Conditions

The use of the Maisotsenko cycle (M-Cycle) in traditional wet cooling towers (TWCTs) has the potential to reduce the costs of electricity generation by cooling water below the inlet air's wet-bulb temperature. TWCTs cannot provide sufficient cooling capacity for the increasing demand for coolin...

Ausführliche Beschreibung

Gespeichert in:
Bibliographische Detailangaben
Veröffentlicht in:Energies (Basel) 2021-12, Vol.14 (24), p.8249, Article 8249
Hauptverfasser: Fan, Xuchen, Lu, Xiaofeng, Wang, Jiping, Li, Zilong, Wang, Quanhai, Dong, Zhonghao, Zhang, Rongdi
Format: Artikel
Sprache:eng
Schlagworte:
Online-Zugang:Volltext
Tags: Tag hinzufügen
Keine Tags, Fügen Sie den ersten Tag hinzu!
Beschreibung
Zusammenfassung:The use of the Maisotsenko cycle (M-Cycle) in traditional wet cooling towers (TWCTs) has the potential to reduce the costs of electricity generation by cooling water below the inlet air's wet-bulb temperature. TWCTs cannot provide sufficient cooling capacity for the increasing demand for cooling energy in the power and industrial sectors-especially in hot and wet climates. Due to this fact, an experimental system of an M-Cycle cooling tower (MCT) with parallel counter-flow arrangement fills was constructed in order to provide perspective on the optimal length of dry channels (l(dry)), thermal performance under different conditions, and pressure drops of the MCT. Results showed that the optimal value of l(dry) was 2.4 m, and the maximum wet-bulb effectiveness was up to 180%. In addition, the impact of air velocity in wet channels on the pressure drops of the novel fills was also summarized. This study confirms the great potential of using the M-Cycle in TWCTs, and provides a guideline for the industrial application and performance improvement of MCTs.
ISSN:1996-1073
1996-1073
DOI:10.3390/en14248249