Stability Analysis of Microgrid Islanding Transients Based on Interconnected Dissipative Subsystems

To ensure successful islanding of microgrids after a fault has occurred, the transient stability should be analyzed under a set of expected operating conditions during the design and operation of microgrids. Transient stability analysis is conventionally performed with time-domain analysis which is...

Ausführliche Beschreibung

Gespeichert in:
Bibliographische Detailangaben
Veröffentlicht in:IEEE transactions on smart grid 2021-11, Vol.12 (6), p.4655-4667
Hauptverfasser: Roos, Martijn H., Nguyen, Phuong H., Morren, Johan, Slootweg, J. G.
Format: Artikel
Sprache:eng
Schlagworte:
Online-Zugang:Volltext bestellen
Tags: Tag hinzufügen
Keine Tags, Fügen Sie den ersten Tag hinzu!
Beschreibung
Zusammenfassung:To ensure successful islanding of microgrids after a fault has occurred, the transient stability should be analyzed under a set of expected operating conditions during the design and operation of microgrids. Transient stability analysis is conventionally performed with time-domain analysis which is computationally expensive and does not quantify the stability margin. Energy-based methodologies can determine the stability margin, however existing methodologies require significant simplifications to be applied to the microgrid model. The energy-based stability analysis methodology proposed in this paper enables the analysis of high-dimension nonlinear microgrid systems and quantification of the stability margin within reasonable time. The performance of the methodology is validated by analyzing a case study microgrid and comparing the results to time-domain analysis and to a state-of-the-art methodology proposed in the literature. The results indicate that the proposed methodology has a significantly lower computational burden and similar accuracy compared to existing energy-based methodologies. The methodology is able to improve the probability of stable islanding of the case study microgrid from 74% up to 94% when only optimizing the design, and up to 100% when optimizing design and control actions.
ISSN:1949-3053
1949-3061
DOI:10.1109/TSG.2021.3100396