Performance study of a heat recovery desiccant cooling system

The comparison between the experimental and theoretical simulations of a desiccant cooling system under various climatic conditions (outdoor temperature and relative humidity) on the system performance has been presented. The performance of the system is evaluated using Cooling Capacity (CC) paramet...

Ausführliche Beschreibung

Gespeichert in:
Bibliographische Detailangaben
Hauptverfasser: Sabek, Seifennasr, Ben Nasr, Kaouther, Chouikh, Ridha, Guizani, Amenallah
Format: Tagungsbericht
Sprache:eng
Schlagworte:
Online-Zugang:Volltext
Tags: Tag hinzufügen
Keine Tags, Fügen Sie den ersten Tag hinzu!
Beschreibung
Zusammenfassung:The comparison between the experimental and theoretical simulations of a desiccant cooling system under various climatic conditions (outdoor temperature and relative humidity) on the system performance has been presented. The performance of the system is evaluated using Cooling Capacity (CC) parameter. The system under a typical summer day of hot and humid climate was tested. A remarkable decrease about 40-65% in the specific humidity and with a supply air temperature lower than 25°C of the proposed system was observed. The study is important and helpful to improve the effectiveness of this kind of liquid desiccant system in hot and humid places.
ISSN:1742-6596
1742-6588
1742-6596
DOI:10.1088/1742-6596/596/1/012016