Computation of ground potential rise and grounding impedance of simple arrangement of electrodes buried in frequency-dependent stratified soil

•Grounding impedance of electrodes in different arrangements are computed for frequency-dependent stratified soils.•A planar multilayer Green’s approach is used to compute the grounding impedance of several topologies.•Ground Potential Rise is significantly reduced for soils of high resistivity with...

Ausführliche Beschreibung

Gespeichert in:
Bibliographische Detailangaben
Veröffentlicht in:Electric power systems research 2021-09, Vol.198, p.107364, Article 107364
Hauptverfasser: de Araújo, Anderson R.J., Colqui, Jaimis S.L., de Seixas, Claudiner M., Kurokawa, Sérgio, Salarieh, Bamdad, Pissolato Filho, José, Kordi, Behzad
Format: Artikel
Sprache:eng
Schlagworte:
Online-Zugang:Volltext
Tags: Tag hinzufügen
Keine Tags, Fügen Sie den ersten Tag hinzu!
Beschreibung
Zusammenfassung:•Grounding impedance of electrodes in different arrangements are computed for frequency-dependent stratified soils.•A planar multilayer Green’s approach is used to compute the grounding impedance of several topologies.•Ground Potential Rise is significantly reduced for soils of high resistivity with frequency-dependence on the electrical parameters. Grounding electrodes are used to provide a low-impedance dissipation path for the excess lightning or fault currents. Several studies have been dedicated to the computation of the grounding impedance of different electrode arrangements considering either the frequency dependence of soil parameters (resistivity ρ and relative permittivity εr) or the multi-layer nature of soil. This paper aims at the calculation of the grounding impedance and the ground potential rise (GPR) of simple electrode arrangements (vertical and cross electrodes) due to the injection of first and subsequent lightning currents in various configurations of soil, considering a frequency-dependent stratified soil. A frequency-domain full-wave electromagnetic solver based on the Method of Moment (MoM) that employs a stratified medium Green’s function is used to compute the grounding impedance in a frequency range of 100Hz to 10MHz. The transient GPRs are computed using the equivalent circuit of the grounding system, obtained through the application of the Vector Fitting (VF) technique and recursive convolution method. The simulation results show that considering the frequency dependence of the soil parameters has no effect on the low-frequency grounding impedance up to ≈10kHz. However, the frequency dependence of soil parameters leads to a considerable variation of the grounding impedance at higher frequencies especially for soils of higher resistivity. Furthermore, it is shown that considering the layers of soil has a more significant impact on the GPR of the vertical electrode than that of the cross electrode.
ISSN:0378-7796
1873-2046
DOI:10.1016/j.epsr.2021.107364