Control of high-voltage pump motor using a frequency sine-wave filter converter
The method of control of a pump motor using a frequency converter as the most promising for saving energy in pumping units is described in the article. The installation of a two-transformer circuit with a low-voltage frequency converter at a pumping station in Krasnoyarsk with three network pumps eq...
Gespeichert in:
Veröffentlicht in: | IOP conference series. Materials Science and Engineering 2018-11, Vol.450 (7), p.72003 |
---|---|
Hauptverfasser: | , , , , |
Format: | Artikel |
Sprache: | eng |
Schlagworte: | |
Online-Zugang: | Volltext |
Tags: |
Tag hinzufügen
Keine Tags, Fügen Sie den ersten Tag hinzu!
|
Zusammenfassung: | The method of control of a pump motor using a frequency converter as the most promising for saving energy in pumping units is described in the article. The installation of a two-transformer circuit with a low-voltage frequency converter at a pumping station in Krasnoyarsk with three network pumps equipped with DASO4-450X high-voltage asynchronous electric motors with a power of 630 kW and a voltage of 6 kV was also tested. The introduction of a two-transformer circuit and a low-voltage frequency converter with the inclusion of a sinus filter reduces the energy costs by 37%, reduces the temperature of the entire pump unit to 44 ° C and reduces the number of stops by 10%. In addition, the use of a frequency converter allows to increase the reliability of the entire system, as well as to reduce the risk of a breakthrough of the pipeline network, which is achieved by automatically maintaining pressure within the specified limits. |
---|---|
ISSN: | 1757-8981 1757-899X 1757-899X |
DOI: | 10.1088/1757-899X/450/7/072003 |