Enhancing Inductive Operation of Low-Capacitance Cascaded H-Bridge StatComs Using Optimal Third-Harmonic Circulating Current

The cascaded H-bridge (CHB) low-capacitance static compensator (LC-StatCom) has a limited operating range in the inductive region compared to a conventional StatCom due to the inherent large oscillations on the capacitor voltages. This limitation constitutes a great drawback of CHB LC-StatComs. This...

Ausführliche Beschreibung

Gespeichert in:
Bibliographische Detailangaben
Veröffentlicht in:IEEE transactions on power electronics 2021-09, Vol.36 (9), p.10788-10800
Hauptverfasser: Rodriguez, Ezequiel, Leyva, Ramon, Liu, Qingxiang, Townsend, Christopher, Farivar, Glen, Ceballos, Salvador, Pou, Josep
Format: Artikel
Sprache:eng
Schlagworte:
Online-Zugang:Volltext bestellen
Tags: Tag hinzufügen
Keine Tags, Fügen Sie den ersten Tag hinzu!
Beschreibung
Zusammenfassung:The cascaded H-bridge (CHB) low-capacitance static compensator (LC-StatCom) has a limited operating range in the inductive region compared to a conventional StatCom due to the inherent large oscillations on the capacitor voltages. This limitation constitutes a great drawback of CHB LC-StatComs. This article presents an effective hardware-free solution to overcome this drawback. The proposed solution is based on the injection of an optimal third-harmonic circulating current to suitably shape the capacitor voltages aiming at avoiding overmodulation. Considering all the effects of the third-harmonic circulating current, the article proposes a reference design that guarantees a prescribed safe operating voltage limit, thus increasing the operational range of the LC-StatCom. The proposed approach takes into account the inherent induced oscillation on the capacitor voltages. This approach has been verified by simulation and experimentally with a laboratory prototype, corroborating the excellent performance that agrees with the theoretical analysis.
ISSN:0885-8993
1941-0107