Simulation study on Air Outlet of Data Center
How to reduce the amount of wasted cooling in corridors and gaps is a problem in data center air conditioning design. Modeling the data center airflow data and simulating the temperature distribution are the prerequisites and key points to solve this problem. This paper uses the optimal idea to esta...
Gespeichert in:
Veröffentlicht in: | Journal of physics. Conference series 2021-04, Vol.1865 (4), p.42096 |
---|---|
1. Verfasser: | |
Format: | Artikel |
Sprache: | eng |
Schlagworte: | |
Online-Zugang: | Volltext |
Tags: |
Tag hinzufügen
Keine Tags, Fügen Sie den ersten Tag hinzu!
|
Zusammenfassung: | How to reduce the amount of wasted cooling in corridors and gaps is a problem in data center air conditioning design. Modeling the data center airflow data and simulating the temperature distribution are the prerequisites and key points to solve this problem. This paper uses the optimal idea to establish a mathematical model to simulate the location of the air conditioning vent. Determine the layout of the computer cabinet based on the analysis of the internal and external environment of the computer cabinet. The external environment analysis is mainly the analysis of several directions: According to the CFD simulation and simulation, the wind speed and tuyere arrangement of the air supply port are compared and the optimal wind speed of the air supply port is obtained. For the problem of the ceiling height and the spacing of the upper air outlet, discuss the method of determining the air supply spacing on the air duct so that the upper air supply can cover all the air inlets of the cabinet to achieve the most reasonable air supply flow. For the numerical simulation and optimization of the airflow organization in the equipment room, it is easy to know that the farther away from the air conditioner, the higher the temperature is relative to the air conditioner, and the wind speed far from the air conditioner is relatively large, so the temperature in the distance is higher. Also, because the hot aisle has no ventilation slots, its temperature must be higher than the cold aisle. Therefore, the temperature in the hot aisle is higher than the ground and the air conditioner is far away. According to the airflow dynamic equation and the K-ε turbulence model equation, the Fluent software is used, and combined with the data given in the data center room, the airflow data is simulated. Finally, the best solution for setting the position of the air conditioning air outlet is given. |
---|---|
ISSN: | 1742-6588 1742-6596 |
DOI: | 10.1088/1742-6596/1865/4/042096 |