Optimization and evaluation of a solar energy, heat pump and desiccant wheel hybrid system in a nearly zero energy building

Traditional conventional air conditioners (CACs) are not applicable to nearly zero energy buildings (NZEBs), especially for residential buildings in regions with a humid climate in China. On the one hand, indoor thermal environment can be significantly affected in buildings by adopting insulations w...

Ausführliche Beschreibung

Gespeichert in:
Bibliographische Detailangaben
Veröffentlicht in:Building simulation 2020-12, Vol.13 (6), p.1291-1303
Hauptverfasser: Tian, Shaochen, Su, Xing, Shao, Xiaolu, Wang, Lei
Format: Artikel
Sprache:eng
Schlagworte:
Online-Zugang:Volltext
Tags: Tag hinzufügen
Keine Tags, Fügen Sie den ersten Tag hinzu!
Beschreibung
Zusammenfassung:Traditional conventional air conditioners (CACs) are not applicable to nearly zero energy buildings (NZEBs), especially for residential buildings in regions with a humid climate in China. On the one hand, indoor thermal environment can be significantly affected in buildings by adopting insulations with higher thermal resistance and air tightness. On the other hand, CACs may not be able to meet the energy requirement of NZEBs when dehumidification is in high demand. Therefore, in this paper, a novel hybrid system, which featured solar panel, a multi-evaporator and multi-condenser heat pump, and a desiccant wheel, i.e., the SHDW system was proposed. The evaporator is for pre-cooling, and the desiccant wheel (DW) for handling the whole moisture load. The regeneration air of DW is heated by heat recovery condenser and the solar panel. By varying the evaporation temperature of HP, the energy performance was evaluated, and compared with that of a typical CAC, for controlling indoor temperature and humidity of a residential NZEB, using TRNSYS. The simulations were conducted for Shanghai (in a humid climate) in summer (July and August) and the transition seasons (June and September). The results showed that, first, the optimized evaporation temperature of the system is determined to be 12 °C and 9 °C, respectively, on a typical day both in summer and the transition seasons. Second, the daily coefficient of performances are 3.4 and 2.4 in summer and in transition seasons, respectively. Third, compared to either the temperature or humidity control mode of the CAC, the proposed SHDW system showed better promise for achieving indoor thermal comfort for residential NZEBs, especially in transition seasons. In a typical weekend, the daily energy consumption of the proposed SHDW system is 9.0% and 12.3% lower than that of the CAC with humidity control mode, respectively, in summer and the transition seasons.
ISSN:1996-3599
1996-8744
DOI:10.1007/s12273-020-0627-0