An experimental investigation on the operational characteristics of a novel direct expansion based air conditioning system with a two-sectioned cooling coil

•A two sectioned direct expansion air conditioning (TS-DXAC) system was proposed.•Inherent operational characteristics of the TS-DXAC system were investigated.•The TS-DXAC system can provide variable sensible and latent cooling capacities.•The results pave a way to the development of controller for...

Ausführliche Beschreibung

Gespeichert in:
Bibliographische Detailangaben
Veröffentlicht in:International journal of refrigeration 2020-10, Vol.118, p.131-138
Hauptverfasser: Yang, Liu, Yan, Huaxia, Deng, Shiming, Li, Weilin
Format: Artikel
Sprache:eng
Schlagworte:
Online-Zugang:Volltext
Tags: Tag hinzufügen
Keine Tags, Fügen Sie den ersten Tag hinzu!
Beschreibung
Zusammenfassung:•A two sectioned direct expansion air conditioning (TS-DXAC) system was proposed.•Inherent operational characteristics of the TS-DXAC system were investigated.•The TS-DXAC system can provide variable sensible and latent cooling capacities.•The results pave a way to the development of controller for indoor air humidity. For controlling indoor thermal environment, only indoor air temperature is usually considered when using conventional direct expansion (DX) based air conditioning (A/C) systems. Therefore, based on the previous experiences in developing novel A/C units to provide an enhanced moisture removal capacity, a novel constant speed DX A/C system with a two-sectioned cooling coil (TS-DXAC) has been proposed. In the proposed TS-DXAC system, to reduce its size, the two sections were arranged in parallel with their respective matching variable speed supply fans, and the mass flow rates for both refrigerant and air to each section could be adjusted. The total air flow rate of the system remained however constant, so as not to affect indoor air flow distribution and occupants’ thermal comfort. The inherent operational characteristics of a prototype experimental TS-DXAC system have been experimentally studied. The study results showed that the variations in the mass flow rates of refrigerant and air to the two sections would result in different combinations of the output total cooling capacity (TCC) and equipment sensible heat ratio (E SHR) from the prototype, and that the TCC – E SHR relationship was constrained within an irregular area. Furthermore, different inlet air temperatures and humidity levels would also influence its inherent operational characteristics as reflected by the changes in the positions and shapes of the irregular areas, with the latter influencing more on the operational characteristics.
ISSN:0140-7007
1879-2081
DOI:10.1016/j.ijrefrig.2020.06.018