Temporary overvoltage suppression in half-wavelength transmission lines during asymmetric faults

•Review on half-wavelength power transmission systems.•Line surge arrester modeling.•Iterative computational routine for exact location of possible overvoltages along the line during asymmetric faults.•Inclusion of line arresters at specific points along the line to contain the overvoltage levels in...

Ausführliche Beschreibung

Gespeichert in:
Bibliographische Detailangaben
Veröffentlicht in:Electric power systems research 2020-01, Vol.178, p.106028, Article 106028
Hauptverfasser: Albuquerque, Felipe Proença, Ribeiro Pereira, Ronaldo F., Marques Costa, Eduardo C., Bartocci Liboni, Luisa H.
Format: Artikel
Sprache:eng
Schlagworte:
Online-Zugang:Volltext
Tags: Tag hinzufügen
Keine Tags, Fügen Sie den ersten Tag hinzu!
Beschreibung
Zusammenfassung:•Review on half-wavelength power transmission systems.•Line surge arrester modeling.•Iterative computational routine for exact location of possible overvoltages along the line during asymmetric faults.•Inclusion of line arresters at specific points along the line to contain the overvoltage levels in the transmission system This paper approaches the principal electric characteristics of half-wavelength transmission lines and possible voltage transients resulted from asymmetric faults. Although this non-conventional AC transmission technique presents some attractive advances for electric power transmission through long distances, when compared to the well-established HVDC systems, some important issues should be investigated on eventual overvoltage levels along half-wavelength transmission lines during temporary asymmetric operation conditions, e.g. phase-to-ground fault and single-phase reclosing. In this research, an iterative computational routine locates the overvoltage points by varying the asymmetric fault location from the sending to the receiving end of the transmission line. This procedure provides a full mapping of the most critical overvoltages as a function of the fault point through the line length. Since the most critical fault occurrences and overvoltage locations are known, an alternative method for overvoltage suppression is proposed by using line surge arresters directly at the phases in parallel with the tower insulators. This technique represents an original method to contain overvoltages at middle sections of half-wavelength transmission lines.
ISSN:0378-7796