A Real-Time Adjustment of Conventional Under-Frequency Load Shedding Thresholds

This letter presents an innovative and easy-to-implement approach for the improvement of conventional under-frequency load shedding, where frequency thresholds are adjusted locally in real time. The proposed method, which would be implemented locally in each under-frequency relay, estimates the fort...

Ausführliche Beschreibung

Gespeichert in:
Bibliographische Detailangaben
Veröffentlicht in:IEEE transactions on power delivery 2019-12, Vol.34 (6), p.2272-2274
Hauptverfasser: Potel, Barnabe, Debusschere, Vincent, Cadoux, Florent, Rudez, Urban
Format: Artikel
Sprache:eng
Schlagworte:
Online-Zugang:Volltext bestellen
Tags: Tag hinzufügen
Keine Tags, Fügen Sie den ersten Tag hinzu!
Beschreibung
Zusammenfassung:This letter presents an innovative and easy-to-implement approach for the improvement of conventional under-frequency load shedding, where frequency thresholds are adjusted locally in real time. The proposed method, which would be implemented locally in each under-frequency relay, estimates the forthcoming frequency evolution and adjusts the predefined frequency thresholds values according to the estimated frequency nadir. As a result, significantly improved frequency response by reducing overshoots can be observed. Concept verification was performed by means of Slovenian power-system model simulations, where the comparison with conventional constant-threshold setting showed a high level of efficiency.
ISSN:0885-8977
1937-4208
DOI:10.1109/TPWRD.2019.2900594