Extensions to standard hold time calculations

The paper extends existing methods of calculating the hold time for a fire extinguishing gas in an enclosure to cover mechanical HVAC systems and wide descending interfaces, and compares the wide descending interface model's predictions with some experimental data. A simple approximation to the...

Ausführliche Beschreibung

Gespeichert in:
Bibliographische Detailangaben
Veröffentlicht in:Fire technology 2000-11, Vol.36 (4), p.266
Hauptverfasser: Dewsbury, J, Whiteley, R A
Format: Artikel
Sprache:eng
Schlagworte:
Online-Zugang:Volltext
Tags: Tag hinzufügen
Keine Tags, Fügen Sie den ersten Tag hinzu!
Beschreibung
Zusammenfassung:The paper extends existing methods of calculating the hold time for a fire extinguishing gas in an enclosure to cover mechanical HVAC systems and wide descending interfaces, and compares the wide descending interface model's predictions with some experimental data. A simple approximation to the measured wide descending interface gives conservative hold time predictions, while the sharp descending interface model used in current standards gives optimistic predictions.
ISSN:0015-2684
1572-8099
DOI:10.1023/A:1015479114491