Study on emergency ventilation for train fire environment in metro interchange tunnel

Metro interchange tunnels have been extensively constructed to meet the requirements of traffic organizations among travel lines. Fire safety issues remain a concern owing to the peculiar building structure and lack of special guidelines from current design standards and norms for ventilation. Focus...

Ausführliche Beschreibung

Gespeichert in:
Bibliographische Detailangaben
Veröffentlicht in:Building and environment 2019-01, Vol.147, p.267-283
Hauptverfasser: Liu, Chang, Zhong, Maohua, Tian, Xiangliang, Zhang, Peihong, Li, Shuwen
Format: Artikel
Sprache:eng
Schlagworte:
Online-Zugang:Volltext
Tags: Tag hinzufügen
Keine Tags, Fügen Sie den ersten Tag hinzu!
Beschreibung
Zusammenfassung:Metro interchange tunnels have been extensively constructed to meet the requirements of traffic organizations among travel lines. Fire safety issues remain a concern owing to the peculiar building structure and lack of special guidelines from current design standards and norms for ventilation. Focusing on this problem, and aiming to establish a safe evacuation environment, we carried out numerical simulations and full-scale experiment to investigate the efficiency of available co-work ventilation modes in eliminating smoke induced by train fire. The numerical model was constructed by Fire Dynamic Simulator 6.3.2, using the parameters of a real tunnel, ventilation systems containing tunnel ventilation fan (TVF), jet fan, ceiling duct, and the available co-work modes among these. The grid size and boundary conditions were verified through full-scale fire experiment and theoretical prediction by comparing the fire plume and ceiling jet flow temperature. The results demonstrate that, the semi-hybrid ventilation mode provides safe evacuation environment to the greatest extent, by utilizing the co-operation of TVFs, jet flow, and downstream ceiling extraction, compared to other modes. This mode effectively eliminated smoke and maintained the temperature, harmful gases, visibility and radiant heat flux at a safe level upstream of the fire. Furthermore, the optimized operation of the ceiling duct improved the smoke discharge efficiency as far as possible downstream of the middle carriage fire. An emergency response plan was eventually proposed for different fire scenarios, including equipment activation and passenger evacuation strategies, providing guidance for rapidly creating safe evacuation path in the interchange tunnel fire environment. •Numerical simulations were carried out in metro interchange tunnel fire environment.•We conducted full-scale fire experiment and theory calculation to verify the numerical model.•The semi-hybrid ventilation was proved to be the most effective co-operated mode for safe evacuation.•The optimized operation for semi-hybrid ventilation was determined.•We proposed the emergency response guide for ventilation and evacuation.
ISSN:0360-1323
1873-684X
DOI:10.1016/j.buildenv.2018.10.022