Harmonic Analysis of Yindong ±660kV HVDC Transmission System

Based on PSCAD/EMTDC simulation platform, this paper analyses the harmonics caused by the process of rectifier and inverter and DC bias of transformer in Yindong ±660kV HVDC transmission system. The results indicate that, characteristic harmonics of 660kV HVDC system AC bus give priority to 12k±1 ti...

Ausführliche Beschreibung

Gespeichert in:
Bibliographische Detailangaben
Veröffentlicht in:Applied Mechanics and Materials 2013-10, Vol.448-453, p.2049-2053
Hauptverfasser: Yuan, Hai Yan, Yun, Yu Xin, Liu, Min
Format: Artikel
Sprache:eng
Schlagworte:
Online-Zugang:Volltext
Tags: Tag hinzufügen
Keine Tags, Fügen Sie den ersten Tag hinzu!
Beschreibung
Zusammenfassung:Based on PSCAD/EMTDC simulation platform, this paper analyses the harmonics caused by the process of rectifier and inverter and DC bias of transformer in Yindong ±660kV HVDC transmission system. The results indicate that, characteristic harmonics of 660kV HVDC system AC bus give priority to 12k±1 time harmonics and bring serious influence to the AC system of the rectifier and converter station; the characteristic harmonics of DC lines are mainly about 12k time and the voltage ripple factor is in the specified scope; both the odd and even harmonic components are increasing significantly under DC bias than that without DC bias,which thereby makes the power transformers become the severe harmonic sources.