Harmonic Analysis of Yindong ±660kV HVDC Transmission System
Based on PSCAD/EMTDC simulation platform, this paper analyses the harmonics caused by the process of rectifier and inverter and DC bias of transformer in Yindong ±660kV HVDC transmission system. The results indicate that, characteristic harmonics of 660kV HVDC system AC bus give priority to 12k±1 ti...
Gespeichert in:
Veröffentlicht in: | Applied Mechanics and Materials 2013-10, Vol.448-453, p.2049-2053 |
---|---|
Hauptverfasser: | , , |
Format: | Artikel |
Sprache: | eng |
Schlagworte: | |
Online-Zugang: | Volltext |
Tags: |
Tag hinzufügen
Keine Tags, Fügen Sie den ersten Tag hinzu!
|
Zusammenfassung: | Based on PSCAD/EMTDC simulation platform, this paper analyses the harmonics caused by the process of rectifier and inverter and DC bias of transformer in Yindong ±660kV HVDC transmission system. The results indicate that, characteristic harmonics of 660kV HVDC system AC bus give priority to 12k±1 time harmonics and bring serious influence to the AC system of the rectifier and converter station; the characteristic harmonics of DC lines are mainly about 12k time and the voltage ripple factor is in the specified scope; both the odd and even harmonic components are increasing significantly under DC bias than that without DC bias,which thereby makes the power transformers become the severe harmonic sources. |
---|---|