Experimental investigation of R410A and R32 falling film evaporation on horizontal enhanced tubes

•Falling film evaporation with nucleating boiling are experimentally studied for R32 and R410A on four doubly enhanced tubes.•HTCs exhibit two stages with decrease of film flow rate, a quasi-plateau stage and a sharp-decrease stage.•HTCs increase with heat flux progressively before reaching the part...

Ausführliche Beschreibung

Gespeichert in:
Bibliographische Detailangaben
Veröffentlicht in:Applied thermal engineering 2018-06, Vol.137, p.739-748
Hauptverfasser: Jin, Pu-Hang, Zhao, Chuang-Yao, Ji, Wen-Tao, Tao, Wen-Quan
Format: Artikel
Sprache:eng
Schlagworte:
Online-Zugang:Volltext
Tags: Tag hinzufügen
Keine Tags, Fügen Sie den ersten Tag hinzu!
Beschreibung
Zusammenfassung:•Falling film evaporation with nucleating boiling are experimentally studied for R32 and R410A on four doubly enhanced tubes.•HTCs exhibit two stages with decrease of film flow rate, a quasi-plateau stage and a sharp-decrease stage.•HTCs increase with heat flux progressively before reaching the partial dryout regime.•The integrated-fin tube performs best among the four enhanced tubes tested. In this study, heat transfer performance on horizontal copper tubes of high pressure refrigerants R32 and R410A was investigated. An integrated fin (condensation enhanced) tube and three boiling enhanced tubes with 3-D different enhancement structures were tested. A plain tube was also tested for comparison. Effects of film flow rate, saturation temperature and heat flux on the falling film heat transfer coefficients were investigated. A tube bundle comprised of 6 enhanced boiling tubes was also tested to find the bundle effect. Experiments were carried out at saturation temperatures of 6, 10 and 16 °C, heat fluxes from 20 to 150 kW·m−2 and film flow rates from 0.01 kg·m−1·s−1 to 0.14 kg·m−1·s−1. It is found that the effect of film Reynolds number on HTCs of enhanced tubes can be separated into two regimes, a quasi-plateau regime and a sharp decrease regime. HTCs increase with heat flux. Increase of saturation temperature has negligible effect on enhanced tubes as well as the tube bundle. The integrated fin tube performs best among the tubes tested. As a whole, R410A is inferior than R32. Tubes positioned below the top row possess the similar variation trend of HTCs with that of the first row but suffer an earlier dryout.
ISSN:1359-4311
1873-5606