DC-link voltage regulation of inverters to enhance microgrid stability during network contingencies
•A drawback of droop control is identified which leads circulating power flow during network contingencies.•A novel over-voltage regulation strategy is proposed in order to prevent an unintentional inverter shutdown.•A small-signal analysis is also performed to evaluate a microgrid's stability....
Gespeichert in:
Veröffentlicht in: | Electric power systems research 2017-06, Vol.147, p.233-244 |
---|---|
Hauptverfasser: | , , , |
Format: | Artikel |
Sprache: | eng |
Schlagworte: | |
Online-Zugang: | Volltext |
Tags: |
Tag hinzufügen
Keine Tags, Fügen Sie den ersten Tag hinzu!
|
Zusammenfassung: | •A drawback of droop control is identified which leads circulating power flow during network contingencies.•A novel over-voltage regulation strategy is proposed in order to prevent an unintentional inverter shutdown.•A small-signal analysis is also performed to evaluate a microgrid's stability.
Equal power-rating inverters operating with different power set-points in either an islanded or grid-connected mode may lead to inter-unit circulating power caused by a large mismatch between power generation and demand during network contingencies (faults on the heavy load side or unintentional islanding). This circulating power may violate the dc-link voltage limit and, as a result, the protection scheme may shut down the inverter and reduce the microgrids reliability. This paper proposes a regulator for controlling the dc-link voltage of the microgrid's inverter during a period of circulating power. It includes a discharging resistor with a series-connected switch across the dc-link capacitor which is turned on through a control algorithm if the dc-link voltage exceeds its pre-defined limit. Case studies of parallel-connected inverters are conducted and their stability assessed through a small-signal analysis. In addition, a realistic microgrid is designed as a low-voltage (LV) network and tested to verify the concept and regulator actions presented. The simulation results validate the effectiveness of the proposed regulator during network contingencies. |
---|---|
ISSN: | 0378-7796 1873-2046 |
DOI: | 10.1016/j.epsr.2017.02.026 |