大学研究施設に導入したリン酸型燃料電池コージェネレーションシステムの性能評価

It is important to effectively utilize the waste heat from the electric generator in order to achieve high overall energy efficiency of cogeneration system (CGS). To examine the energy conservation efficiency of CGS on the actual situation, we have researched the operative situation of the PAFC-CGS...

Ausführliche Beschreibung

Gespeichert in:
Bibliographische Detailangaben
Veröffentlicht in:AIJ journal of technology and design 2017, Vol.23(54), pp.553-556
Hauptverfasser: 佐藤, 久明, 浅野, 良晴, 岩井, 一博
Format: Artikel
Sprache:jpn
Schlagworte:
Online-Zugang:Volltext
Tags: Tag hinzufügen
Keine Tags, Fügen Sie den ersten Tag hinzu!
Beschreibung
Zusammenfassung:It is important to effectively utilize the waste heat from the electric generator in order to achieve high overall energy efficiency of cogeneration system (CGS). To examine the energy conservation efficiency of CGS on the actual situation, we have researched the operative situation of the PAFC-CGS that has been installed in the new building in the university. As a result, the primary energy consumption of the building was found to be 52.8% less compared to the benchmarks of DECC. And the annual average of the thermal efficiency of the PAFC-CGS was found to be 0.54.
ISSN:1341-9463
1881-8188
DOI:10.3130/aijt.23.553