On the dependence between the amplitude and time parameters of pulse voltages in general-purpose power-supply systems
The existing regulatory requirements to assessment of the voltage pulses in general-purpose power-supply systems as a parameter of electric energy quality are considered. The attention is focused on the fact that GOST (State Standard) 32144-2013 recommends taking into account the statistics related...
Gespeichert in:
Veröffentlicht in: | Russian electrical engineering 2017-08, Vol.88 (8), p.480-484 |
---|---|
Hauptverfasser: | , , , |
Format: | Artikel |
Sprache: | eng |
Schlagworte: | |
Online-Zugang: | Volltext |
Tags: |
Tag hinzufügen
Keine Tags, Fügen Sie den ersten Tag hinzu!
|
Zusammenfassung: | The existing regulatory requirements to assessment of the voltage pulses in general-purpose power-supply systems as a parameter of electric energy quality are considered. The attention is focused on the fact that
GOST
(State Standard)
32144-2013
recommends taking into account the statistics related to such characteristics when concluding contracts for electric-energy supply or transmission. The article presents the results of processing of the statistical material obtained using a special device for recording the impulse-voltage parameters. A stable correlation and regression dependence between these parameters has been established. It is shown that this dependence has an exponential character. A method of generating a test voltage pulse is proposed to test the actual resistance of consumers to impulse voltages arising in the power supply circuits. |
---|---|
ISSN: | 1068-3712 1934-8010 |
DOI: | 10.3103/S1068371217080053 |