Cooling capacity and acoustic performance of radiant slab systems with free-hanging acoustical clouds
[Display omitted] •We tested different coverage areas of acoustical clouds below a radiant ceiling.•We experimentally assessed the cooling capacity in a hydronic test chamber.•We experimentally assessed the sound absorption in a reverberation chamber.•The cooling capacity coefficient decreases by 11...
Gespeichert in:
Veröffentlicht in: | Energy and buildings 2017-03, Vol.138, p.676-686 |
---|---|
Hauptverfasser: | , , , , , |
Format: | Artikel |
Sprache: | eng |
Schlagworte: | |
Online-Zugang: | Volltext |
Tags: |
Tag hinzufügen
Keine Tags, Fügen Sie den ersten Tag hinzu!
|
Zusammenfassung: | [Display omitted]
•We tested different coverage areas of acoustical clouds below a radiant ceiling.•We experimentally assessed the cooling capacity in a hydronic test chamber.•We experimentally assessed the sound absorption in a reverberation chamber.•The cooling capacity coefficient decreases by 11% for 47% cloud coverage.•We can achieve an acceptable reverberation time with 47% cloud coverage.
Radiant slab systems have the potential to achieve significant energy savings, yet, when applied in the ceiling (e.g., thermally activated building system) the exposed concrete may also create acoustical challenges due to the high reflectivity of the hard surface. Balancing all of the building indoor environmental quality factors is important in the design of an effective workspace for the occupants, and so we need to consider the interactions between thermal and acoustic comfort. We assessed the cooling capacity in a hydronic test chamber and the sound absorption in a reverberation chamber to study the effects, for an office room, of different coverage areas of free-hanging acoustical clouds below a radiant chilled ceiling. The cooling experiments showed that for 47% cloud coverage of the ceiling area, we measured only an 11% reduction in cooling capacity caused by the blockage of radiant exchange between the ceiling and the room. The acoustical results showed that if the cloud covered 30% of the ceiling in a private office or 50% in an open plan office, acceptable sound absorption at the ceiling was achieved. We showed that good acoustic quality can be achieved with only a minor reduction of cooling capacity. |
---|---|
ISSN: | 0378-7788 1872-6178 |