An Islanding Detection Method for Multi-DG Systems Based on High-Frequency Impedance Estimation

Active islanding detection methods are generally employed for grid-connected inverter-based distributed generation (DG). However, there might be mutual influences and power quality issues caused by the disturbance signal when multiple inverters are involved. To address those problems, this paper ana...

Ausführliche Beschreibung

Gespeichert in:
Bibliographische Detailangaben
Veröffentlicht in:IEEE transactions on sustainable energy 2017-01, Vol.8 (1), p.74-83
Hauptverfasser: Jia, Ke, Wei, Hongsheng, Bi, Tianshu, Thomas, David W. P., Sumner, Mark
Format: Artikel
Sprache:eng
Schlagworte:
Online-Zugang:Volltext bestellen
Tags: Tag hinzufügen
Keine Tags, Fügen Sie den ersten Tag hinzu!
Beschreibung
Zusammenfassung:Active islanding detection methods are generally employed for grid-connected inverter-based distributed generation (DG). However, there might be mutual influences and power quality issues caused by the disturbance signal when multiple inverters are involved. To address those problems, this paper analyzes the potential failure mechanism of the f-Q (frequency-reactive power) drifting active method in multiple-DG situations. Then, a novel high-frequency transient injection-based islanding detection method that is suitable for both single and multiple DGs is proposed. Compared with the conventional injection methods, a high-frequency impedance model for DG is provided for better theoretical analysis. By means of the intermittent time-domain low-voltage condition injection control, this method can achieve good accuracy and reduce disturbances to power system.
ISSN:1949-3029
1949-3037
DOI:10.1109/TSTE.2016.2582846