Analysis of air-to-water heat pump in cold climate: comparison between experiment and simulation

Heat pump systems are promising technologies for current and future buildings and this research presents the performance of air source heat pump (ASHP) system. The system was monitored, analysed and simulated using TRNSYS software. The experimental data were used to calibrate the simulation model of...

Ausführliche Beschreibung

Gespeichert in:
Bibliographische Detailangaben
Veröffentlicht in:Science future of Lithuania 2015-09, Vol.7 (4), p.468-474
Hauptverfasser: Janusevicius, Karolis, Streckiene, Giedre
Format: Artikel
Sprache:eng ; lit
Schlagworte:
Online-Zugang:Volltext
Tags: Tag hinzufügen
Keine Tags, Fügen Sie den ersten Tag hinzu!
Beschreibung
Zusammenfassung:Heat pump systems are promising technologies for current and future buildings and this research presents the performance of air source heat pump (ASHP) system. The system was monitored, analysed and simulated using TRNSYS software. The experimental data were used to calibrate the simulation model of ASHP. The specific climate conditions are evaluated in the model. It was noticed for the heating mode that the coefficient of performance (COP) varied from 1.98 to 3.05 as the outdoor temperature changed from –7.0 ºC to +5.0 ºC, respectively. TRNSYS simulations were also performed to predict seasonal performance factor of the ASHP for Vilnius city. It was identified that seasonal performance prediction could be approximately 15% lower if frost formation effects are not included to air-water heat pump simulation model.
ISSN:2029-2341
2029-2252
DOI:10.3846/mla.2015.823