A Modified LLCL Filter With the Reduced Conducted EMI Noise

For a transformerless grid-tied converter using pulse width modulation, the harmonics of grid-injected current, the leakage current, and the electromagnetic interference (EMI) noise are three important issues during designing of the output filter. In this paper, the common mode and the differential...

Ausführliche Beschreibung

Gespeichert in:
Bibliographische Detailangaben
Veröffentlicht in:IEEE transactions on power electronics 2014-07, Vol.29 (7), p.3393-3402
Hauptverfasser: Weimin Wu, Yunjie Sun, Zhe Lin, Yuanbin He, Min Huang, Blaabjerg, Frede, Chung, Henry Shu-hung
Format: Artikel
Sprache:eng
Schlagworte:
Online-Zugang:Volltext bestellen
Tags: Tag hinzufügen
Keine Tags, Fügen Sie den ersten Tag hinzu!
Beschreibung
Zusammenfassung:For a transformerless grid-tied converter using pulse width modulation, the harmonics of grid-injected current, the leakage current, and the electromagnetic interference (EMI) noise are three important issues during designing of the output filter. In this paper, the common mode and the differential mode EMI noises are investigated for the LCL- and LLCL-filter-based single-phase full-bridge grid-tied inverters. Based on this, a modified LLCL-filter topology is proposed to provide enough attenuation on the conducted EMI noise as well as to reduce the dc-side leakage current. The parameter design method of the filter is also developed. The comparative analysis and discussion on four filter cases (the conventional LCL filter, the conventional LLCL filter, the modified LCL filter, and the modified LLCL filter) are carried out and verified through simulations and experiments on a 0.5-kW, 110 V/50 Hz single-phase full-bridge grid-tied inverter prototype.
ISSN:0885-8993
1941-0107