Ventilation Measurement and Simulation Optimization for Aerobic Composting Workshop of a Large Sludge Treatment Engineering

Based on measured ventilation condition in the built aerobic composting plant of large sludge treatment engineering,using the methord of CFD, four kinds of scheme for the new aerobic composting plant were analysed,which contain two types of ventilation(natural air supply mechanical exhaust and mecha...

Ausführliche Beschreibung

Gespeichert in:
Bibliographische Detailangaben
Veröffentlicht in:Applied Mechanics and Materials 2012-01, Vol.170-173, p.2727-2731
Hauptverfasser: Jia, Shuang, Zhang, Li Juan, Zhang, Jian Fei, Du, Xu, Zhu, Kai Zhen
Format: Artikel
Sprache:eng
Online-Zugang:Volltext
Tags: Tag hinzufügen
Keine Tags, Fügen Sie den ersten Tag hinzu!
Beschreibung
Zusammenfassung:Based on measured ventilation condition in the built aerobic composting plant of large sludge treatment engineering,using the methord of CFD, four kinds of scheme for the new aerobic composting plant were analysed,which contain two types of ventilation(natural air supply mechanical exhaust and mechanical air mechanical ventilation)and two kinds of supply air rates (4x105m3/h and 8x105m3/h). Studies have shown that the methord of mechanical air supply and exhaust is better than the original natural air mechanical exhaust in this plant; The methord of mechanical air supply and exhaust is recommended to reduce ammonia content for personal breathing zone and ventilation energy consumption.
ISSN:1660-9336
1662-7482
1662-7482
DOI:10.4028/www.scientific.net/AMM.170-173.2727