Construction and Analysis of Personalized Air-Conditioning System

This study applied the thermoelectric chip design and the establishment of the personalized air-conditioning system in the design of the single duct and double duct structures. According to the actual measurement results when the ambient temperature was 29°C, the air outlet temperature of the two st...

Ausführliche Beschreibung

Gespeichert in:
Bibliographische Detailangaben
Veröffentlicht in:Applied Mechanics and Materials 2013-08, Vol.368-370, p.615-618
Hauptverfasser: Lin, Jin Shyong, Chen, Cheng Ho, Hung, Tsung Hsin, Luo, Win Jet, Chung, Chien Wen
Format: Artikel
Sprache:eng
Online-Zugang:Volltext
Tags: Tag hinzufügen
Keine Tags, Fügen Sie den ersten Tag hinzu!
Beschreibung
Zusammenfassung:This study applied the thermoelectric chip design and the establishment of the personalized air-conditioning system in the design of the single duct and double duct structures. According to the actual measurement results when the ambient temperature was 29°C, the air outlet temperature of the two structures was 22°C, 24°C respectively; the power consumption was 133W, 134W respectively. FLUENT was used to simulate the spatial flow field and temperature field for comparison to learn about the spatial temperature distribution status of the air-conditioning system.