Development of a Voltage Sag Detection Method for Non-Utility Generation System

This paper deals with a new detection method based on 3-phase vector operation for voltage sag. The detection method is applicable to a protection system using a high speed interruption system which protects distributed generators and critical loads in a customer’s facility. First, the algorithm and...

Ausführliche Beschreibung

Gespeichert in:
Bibliographische Detailangaben
Veröffentlicht in:Denki Gakkai ronbunshi. B, Enerugi, denki kiki, denryoku 2004, Vol.124(4), pp.531-536
Hauptverfasser: Uchiyama, Noriyuki, Oono, Yasunori, Fujita, Yasunobu
Format: Artikel
Sprache:eng
Schlagworte:
Online-Zugang:Volltext
Tags: Tag hinzufügen
Keine Tags, Fügen Sie den ersten Tag hinzu!
Beschreibung
Zusammenfassung:This paper deals with a new detection method based on 3-phase vector operation for voltage sag. The detection method is applicable to a protection system using a high speed interruption system which protects distributed generators and critical loads in a customer’s facility. First, the algorithm and merits of this method are explained in detail. Secondly, the detection characteristics are analyzed using the ATP (Alternative Transients Program) and are confirmed using a real time digital simulator, and it is shown that the method is useful for detecting voltage sag.
ISSN:0385-4213
1348-8147
DOI:10.1541/ieejpes.124.531