Study on Required Performance of Fault Current Limiter for Dispersed Generator

It is expected that a number of dispersed generators interconnecting with power distribution systems will be increased with progress of deregulation in electric power industry. In order to allow large capacity of the interconnection, a certain current limitation measure is required in present distri...

Ausführliche Beschreibung

Gespeichert in:
Bibliographische Detailangaben
Veröffentlicht in:Denki Gakkai ronbunshi. B, Enerugi, denki kiki, denryoku 2004, Vol.124(1), pp.15-22
Hauptverfasser: Genji, Takamu, Miyazato, Kenji, Tsutsushio, Hidefumi, Nishiwaki, Tadao
Format: Artikel
Sprache:eng
Schlagworte:
Online-Zugang:Volltext
Tags: Tag hinzufügen
Keine Tags, Fügen Sie den ersten Tag hinzu!
Beschreibung
Zusammenfassung:It is expected that a number of dispersed generators interconnecting with power distribution systems will be increased with progress of deregulation in electric power industry. In order to allow large capacity of the interconnection, a certain current limitation measure is required in present distribution systems because of allowable short circuit capacity as a restriction. One of effective measures is fault current limiter (FCL) which suppress short circuit current within a time of half cycle. However, a required performance of FCL applied to dispersed generators is not made clear. The authors look for necessary conditions on the FCL performance for above-mentioned purpose using EMTP simulation. This paper presents necessary performance of FCL, which includes a commutation type FCL with resistance and reactance as a limitation element.