Surge and High-Frequency Propagation in Industrial Power Lines

Laboratory measurements were made on a three-conductor line, with or without steel conduit sheath (typical of single-phase 120/240-V systems), to determine the attenuation of surges and the response to steady excitation at frequencies in the range of 100 Hz-10 MHz. Line length ranged from 75 to 225...

Ausführliche Beschreibung

Gespeichert in:
Bibliographische Detailangaben
Veröffentlicht in:IEEE Trans. Ind. Appl.; (United States) 1986-07, Vol.IA-22 (4), p.634-640
Hauptverfasser: Martzloff, Francois D., Gauper, Harold A.
Format: Artikel
Sprache:eng
Schlagworte:
Online-Zugang:Volltext bestellen
Tags: Tag hinzufügen
Keine Tags, Fügen Sie den ersten Tag hinzu!
Beschreibung
Zusammenfassung:Laboratory measurements were made on a three-conductor line, with or without steel conduit sheath (typical of single-phase 120/240-V systems), to determine the attenuation of surges and the response to steady excitation at frequencies in the range of 100 Hz-10 MHz. Line length ranged from 75 to 225 m. Impedance matching was maintained at the sending end, while at the receiving end various loads (matched or mismatched) were included. A nonlinear load was also used, illustrating the side effects of connecting a surge protective device at the end of the line.
ISSN:0093-9994
1939-9367
DOI:10.1109/TIA.1986.4504773