Parametric identification in potential transformer modelling
It is shown that a wideband lumped parameter equivalent circuit of a potential transformer can be determined through parametric system identification by the least squares method. Because of limitations in the measuring equipment, up to four different sets of input/output signals are necessary. Compa...
Gespeichert in:
Veröffentlicht in: | IEEE transactions on power delivery 1992-01, Vol.7 (1), p.70-76 |
---|---|
Hauptverfasser: | , , , |
Format: | Artikel |
Sprache: | eng |
Schlagworte: | |
Online-Zugang: | Volltext bestellen |
Tags: |
Tag hinzufügen
Keine Tags, Fügen Sie den ersten Tag hinzu!
|
Zusammenfassung: | It is shown that a wideband lumped parameter equivalent circuit of a potential transformer can be determined through parametric system identification by the least squares method. Because of limitations in the measuring equipment, up to four different sets of input/output signals are necessary. Compared with other tests for finding the equivalent circuit, this method is less time consuming. Results obtained on a 50 Hz (20/ square root 3) kV/(110/ square root 3) V potential transformer are presented.< > |
---|---|
ISSN: | 0885-8977 1937-4208 |
DOI: | 10.1109/61.108891 |