Modeling of LCC-HVDC Systems Using Dynamic Phasors
This paper presents an average-value model of a line-commutated converter-based HVDC system using dynamic phasors. The model represents the low-frequency dynamics of the converter and its ac and dc systems, and has lower computational requirements than a conventional electromagnetic-transient (EMT)...
Gespeichert in:
Veröffentlicht in: | IEEE transactions on power delivery 2014-08, Vol.29 (4), p.1989-1998 |
---|---|
Hauptverfasser: | , , , , , , , , , |
Format: | Artikel |
Sprache: | eng |
Schlagworte: | |
Online-Zugang: | Volltext bestellen |
Tags: |
Tag hinzufügen
Keine Tags, Fügen Sie den ersten Tag hinzu!
|
Zusammenfassung: | This paper presents an average-value model of a line-commutated converter-based HVDC system using dynamic phasors. The model represents the low-frequency dynamics of the converter and its ac and dc systems, and has lower computational requirements than a conventional electromagnetic-transient (EMT) switching model. The developed dynamic-phasor model is verified against an EMT model of the CIGRE HVDC Benchmark. Simulation results confirm the validity and accuracy of the average value model in predicting the low-frequency dynamics of the ac- and dc-side quantities. Merits and applicability limitations of the average model are highlighted. |
---|---|
ISSN: | 0885-8977 1937-4208 |
DOI: | 10.1109/TPWRD.2014.2308431 |