Current Interruption in Air for a Medium-Voltage Load Break Switch

The current interrupting capability of a load break switch (LBS) depends on many design parameters, such as contact and nozzle geometry, contact movement, and gas flow. For developing more compact gas blow LBSs for air, it is necessary to find design recommendations where each parameter is addressed...

Ausführliche Beschreibung

Gespeichert in:
Bibliographische Detailangaben
Veröffentlicht in:IEEE transactions on power delivery 2014-04, Vol.29 (2), p.870-875
Hauptverfasser: Jonsson, Erik, Aanensen, Nina Sasaki, Runde, Magne
Format: Artikel
Sprache:eng
Schlagworte:
Online-Zugang:Volltext bestellen
Tags: Tag hinzufügen
Keine Tags, Fügen Sie den ersten Tag hinzu!
Beschreibung
Zusammenfassung:The current interrupting capability of a load break switch (LBS) depends on many design parameters, such as contact and nozzle geometry, contact movement, and gas flow. For developing more compact gas blow LBSs for air, it is necessary to find design recommendations where each parameter is addressed individually. In this paper, a current interruption test switch is built for this purpose. The interruption tests are conducted with a directly powered high-voltage circuit. The result shows the minimum gas flow required for current interruption for various basic nozzle geometries and at different contact positions. The study is particular relevant for the 24 kV/630 A class, and it is shown that 0.3 bar upstream pressure appears to be a threshold value for successful interruption. Some conclusions are also applicable for other medium-voltage ratings. An LBS should be designed so that at least one current zero crossing comes outside the nozzle when the switch is still blowing with full strength.
ISSN:0885-8977
1937-4208
DOI:10.1109/TPWRD.2013.2280300