High Altitude Effect on Corona Inception Voltages of DC Power Transmission Conductors Based on the Mobile Corona Cage

In order to investigate the high altitude effect on dc corona inception voltage of power transmission lines, a mobile corona cage test system was constructed. The experiments were carried in Wuhan, Xining, Geermu, and Nachitai, respectively. Photons released as a result of corona discharge on the co...

Ausführliche Beschreibung

Gespeichert in:
Bibliographische Detailangaben
Veröffentlicht in:IEEE transactions on power delivery 2013-07, Vol.28 (3), p.1971-1973
Hauptverfasser: Xingming Bian, Liming Wang, Yunpeng Liu, Yingjian Yang, Zhicheng Guan
Format: Artikel
Sprache:eng
Schlagworte:
Online-Zugang:Volltext bestellen
Tags: Tag hinzufügen
Keine Tags, Fügen Sie den ersten Tag hinzu!
Beschreibung
Zusammenfassung:In order to investigate the high altitude effect on dc corona inception voltage of power transmission lines, a mobile corona cage test system was constructed. The experiments were carried in Wuhan, Xining, Geermu, and Nachitai, respectively. Photons released as a result of corona discharge on the conductors were detected by the ultraviolet image detector. Both positive and negative corona inception voltages could be acquired by the "tangent method" based on the measured data. The approximate linear altitude correction formulas were suggested.
ISSN:0885-8977
1937-4208
DOI:10.1109/TPWRD.2013.2258818