Pressure Drop Analysis of Steam Condensation in a Plate Heat Exchanger

In cooperation with Alfa Laval Thermal AB Company in Sweden, a steam condensation test rig of a plate heat exchanger (PHE) was set up. The heat transfer and pressure drop characteristics of two kinds of typical operation condition in a PHE were obtained: complete condensation and partial condensatio...

Ausführliche Beschreibung

Gespeichert in:
Bibliographische Detailangaben
Veröffentlicht in:Heat transfer engineering 1999-02, Vol.20 (1), p.71-77
Hauptverfasser: WANG, L. K, SUNDEN, B, YANG, Q. S
Format: Artikel
Sprache:eng
Schlagworte:
Online-Zugang:Volltext
Tags: Tag hinzufügen
Keine Tags, Fügen Sie den ersten Tag hinzu!
Beschreibung
Zusammenfassung:In cooperation with Alfa Laval Thermal AB Company in Sweden, a steam condensation test rig of a plate heat exchanger (PHE) was set up. The heat transfer and pressure drop characteristics of two kinds of typical operation condition in a PHE were obtained: complete condensation and partial condensation. This article introduces the test rig, various sensors, and the data acquisition system used in the measurements. The process of steam condensation in a PHE is analyzed in detail. The two-phase frictional pressure drop along this wavy channel was obtained from the measured steam condensation pressure drop. The Lockhart-Martinelli model was extended to predict the pressure drop of steam condensation in a PHE and was verified by the experimental results. Based on the data processing of 109 experimental points, a correlation of frictional pressure drop of steam condensation in a PHE is suggested. This correlation is recommended for calculation of the steam condensation pressure drop in a PHE.
ISSN:0145-7632
1521-0537
DOI:10.1080/014576399271727